Eksperimentalno proučavanje odmrzavanja toplim vazduhom isparivača toplotne pumpe
##plugins.themes.bootstrap3.article.main##
Apstrakt
Odmrzavanje isparivača toplotne pumpe toplim vazduhom eksperimentalno je istraživano u kontrolisanim uslovima, u klimatizovanom vetrenom tunelu. Ovaj posao je zapošet radi nalaženja mogućnosti odmrzavanja isparivača u uslovima u kojima toplotna pumpa ne prestaje da greje. Pri tome je korišćen jedan četvororedni razmenjivač toplote sa pravim rebrima, odozdo snabdeven pretvaračem šarže, radi merenja promene težine i tokom stvaranja leda i njegovog uklanjanja. Stepen otapanja je određivan kao funkcija temperature vazduha, relativne vlažnosti i brzine. Nađeno je da uklanjanje vode, stvorene odmrzavanjem, sa površine razmenjivača, zavisi od brzine vazduha.
##plugins.themes.bootstrap3.article.details##
Kako citirati
AMEEN, F. R.; CONEY, J. E.R.; SHEPPARD, C. G.W..
Eksperimentalno proučavanje odmrzavanja toplim vazduhom isparivača toplotne pumpe.
KGH – Klimatizacija, grejanje, hlađenje, [S.l.], v. 23, n. 2, p. 31-35, nov. 2016.
ISSN 2560-340X.
Dostupno na: <https://izdanja.smeits.rs/index.php/kgh/article/view/444>. Datum pristupa: 11 oct. 2026
Broj časopisa
Sekcija
Tematski članci
Reference
[1] Ammeen, F.R., Cone Y. J.E.R., Shepard, C.G.W: An experimental study of melting ice cylinders in a warm-air cross flow, Int. J. Refrig. (1991),14(3),168-175.
[2] Stoecker, W. F.: How frost formation on coils affects refrigeration systems, Refrig. Engng. (1957),45, 42-44.
[3] Taplin, B.E. : Effect of frost on extended surface evaporators. Austral. Refrig., Air Cond. Heating J. (Avgust 1964), 27-35.
[4] Hayashi, Y. Aoki, A., Adachi, S., Hori, K.: Study of frost properties correlating with frost formation types, ASMF J. Heat Transfer (1977), 99, 239-245.
[5] McQuiSton, F.C.: Heat mass and momentum transfer in a parallel plate dehumidifying exchanger, ASHRAE Trans. (1974), 82 (2), 87-104.
[6] Eckles, P.W., Q., Rabas, T.J.: Dehumidification: on the correlation of wet and dry transport processes in plate finned-tube heat exchanger, ASME J. Heat Transfer (1987), 109, 575-582.
[7] Kuwahara, E., Kawamura T,. Yamazaki, M.: Shortening the defrost time on a heat pump air conditioner, ASHRAE Trans. (1986), 92, 20-29.
[8] Willins, R.E., Griskey, R.G.: Mass transfer from cylinder at various orientation to flowing gas streams, Can.J.Chem. Engng. (1975), 53, 500-504.
[2] Stoecker, W. F.: How frost formation on coils affects refrigeration systems, Refrig. Engng. (1957),45, 42-44.
[3] Taplin, B.E. : Effect of frost on extended surface evaporators. Austral. Refrig., Air Cond. Heating J. (Avgust 1964), 27-35.
[4] Hayashi, Y. Aoki, A., Adachi, S., Hori, K.: Study of frost properties correlating with frost formation types, ASMF J. Heat Transfer (1977), 99, 239-245.
[5] McQuiSton, F.C.: Heat mass and momentum transfer in a parallel plate dehumidifying exchanger, ASHRAE Trans. (1974), 82 (2), 87-104.
[6] Eckles, P.W., Q., Rabas, T.J.: Dehumidification: on the correlation of wet and dry transport processes in plate finned-tube heat exchanger, ASME J. Heat Transfer (1987), 109, 575-582.
[7] Kuwahara, E., Kawamura T,. Yamazaki, M.: Shortening the defrost time on a heat pump air conditioner, ASHRAE Trans. (1986), 92, 20-29.
[8] Willins, R.E., Griskey, R.G.: Mass transfer from cylinder at various orientation to flowing gas streams, Can.J.Chem. Engng. (1975), 53, 500-504.